New refrigeration technology: what has changed, what has remained the same

New refrigeration technology with more power in the low temperature range

Our new CO2 refrigeration technology achieves a test chamber temperature of up to −50°C in our climate chambers and temperature chambers. It is more powerful in the low temperature range than the previous −40°C refrigeration technology. At the critical point of −40°C for many test standards, the new refrigerating units still provide considerable cooling capacity and heat compensation. Traditional, single-stage refrigeration technology can hardly cool test specimens below −30°C.

In all Weiss Technik test chambers, the previous −40°C refrigeration technology is being replaced by new CO2-based refrigeration technology without changing the design, connections, and dimensions of the units. The environmental parameters also remain the same. Infrastructure such as cooling water, connectors, and accessories can continue to be used. Only a few technical parameters have changed.


units with CO2 refrigeration technology

New: Fuses with 300mA required due to frequency converters

The cooling water temperature remains the same: 12-28°C.

Ambient temperatures of up to 35°C are no problem.

The dimensions, size and footprint of all appliances remain the same.

The new Simpac 2.0 controller has a ring buffer, Linux, and NTP.

An electronic cooling water regulator allows a lower water pressure.

The new CO2 refrigeration technology can cool down to -50°C.

Power consumption and power consumption are lower than before.

Lower sound pressure level: CO2 refrigeration has smaller, quieter components.

IEC 60068-2-14 Nb: Sufficient heat compensation in the holding phase at -40°C. No cascade system necessary.

System pressure up to 120 bar, but significantly smaller cross-sections and volumes. No problem with the Pressure Equipment Directive.

CO2 has GWP1 and is not flammable.

Parameterprevious −40°C classnew CO2 refrigeration
Refrigerant GWP13971
Energy consumptionlower
Sound pressure levelquieter
Rate of temperature change, cooling guaranteed up to−18°C−27°C
Temporal temperature deviation0.1–0.5 K0.1–0.5 K
Spatial temperature homogeneity0.5–1 K0.5–1 K
Cooling water temperature12–28°C12–28°C
Ambient temperature28/35°C28/35°C
Footprintidentical
Installation room (practical limit value)2.8 m³ per kg R449A14 m³ per kg CO2
Pressure equipment categoryNoneNone
S!MPATI® portsadditionally 62542 for ASCII 2050 & 2051
−40°C class (no longer available from 2025) CO2 class (now available) −70°C class (still available)
LabEvent (temperature/climate)    
20 tba 2025 --
34  5 K/min −40°C  x K/min −70°C  5 K/min
64  3 K/min −40°C  x K/min −70°C  3 K/min
100  5 K/min −50°C  4 K/min −70°C  3 K/min & 10 K/min
150  5 K/min −50°C  x K/min −70°C  3 K/min & 10 K/min
210  3 K/min −50°C  x K/min −70°C  3 K/min & 5 K/min
500  −30°C   3 K/min −50°C 3 K/min & 6 K/min −60°C  3 K/min
     
ClimeEvent & TempEvent    
180    3 K/min & 5 K/min 3 K/min & 8 K/min 3 K/min & 5 K/min
340    3 K/min & 5 K/min 3 K/min & 6 K/min 3 K/min & 5 K/min
600    3 K/min & 5 K/min 3 K/min & 9 K/min 3 K/min & 5 K/min
1000   3 K/min & 5 K/min 7 K/min & 13 K/min 3 K/min & 5 K/min
1500   3 K/min & 5 K/min 5 K/min 3 K/min & 5 K/min
2000   3 K/min tba 2025 3 K/min
270    10, 15, 20 K/min   10, 15, 20, 25 K/min
480    10, 15, 20 K/min   10, 15, 20, 25 K/min
800    10, 15, 20 K/min   10, 15, 20, 25 K/min
1300  10, 15, 20 K/min   10, 15, 20, 25 K/min
     
XXL 1600  3 K/min & 5 K/min −50°C  >4 K/min 3 K/min & 5 K/min
XXL 2450  3 K/min & 5 K/min −50°C  >3 K/min 2 K/min & 4 K/min
XXL 3400  3 K/min & 5 K/min −50°C  >2 K/min 2 K/min & 4 K/min
     
Walk-in (9–21 m³) all −50°C (>2 K/min) All sizes -70°C (>2 K/min)

 

The performance values are measured according to IEC 60068-3-5 in the range of 10–90% of the entire temperature range.

All our appliances with special functions will also be available with CO2 refrigeration from 2025:

  • ShakeEvent 
  • SunEvent
  • AirEvent Gas & AirEvent Ozone 
  • Constant climate chambers 
  • R-chambers

 

Many rapid coolers (>10 K/min) are available with CO2 and are measured on request.

All models are available on request without F-gas, some with longer delivery times.